CHWJK - SEALED, LEAD-CALCIUM BATTERY, LS 2-600

  • MSDS: CHWJK
  • Manufacturer: C AND D TECHNOLOGIES INC
  • Product Name: SEALED, LEAD-CALCIUM BATTERY, LS 2-600
  • National Stock Number: 6140-00N089615
Product Identification

Product ID:SEALED, LEAD-CALCIUM BATTERY, LS 2-600
MSDS Date:12/05/1997
FSC:6140
NIIN:00N089615
Status Code:A
MSDS Number: CHWJK

Responsible Party
C & D TECHNOLOGIES INC
1400 UNION MEETING RD
BLUE BELL, PA 19422-0858
US

Emergency Phone: 800-255-3924

Info Phone: 215-619-2700

Preparer: S J KELLY

Cage: 1CTA5

Contractor
C & D TECHNOLOGIES INC
3053 BLUE BELL, PA 19422-0858 US

Telephone: 215-619-2700

Cage: 1CTA5

Ingredients

LEAD (SARA 313) (CERCLA)

CAS: 7439-92-1

RTECS: OF7525000

Fraction By Weight: 66-77%

OSHA PEL SEE 1910.1025

ACGIH TLV: 0.15MG/M3 DUST; 9495

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


SULFURIC ACID (SARA 302/313) (CERCLA)

CAS: 7664-93-9

RTECS: WS5600000

Fraction By Weight: 6-9%

OSHA PEL 1 MG/M3

ACGIH TLV: 1 MG/M3/3 STEL; 9495

EPA Report Quantity: 1000 LBS

DOT Report Quantity: 1000 LBS


TIN

CAS: 7440-31-5

RTECS: XP7320000

Fraction By Weight: 0.1-0.3%

OSHA PEL 2 MG/M3

ACGIH TLV: 2 MG/M3; 9495


ALUMINUM (SARA 313)

CAS: 7429-90-5

RTECS: BD0330000

Fraction By Weight: <0.01%

OSHA PEL 15 MG/M3 DUST

ACGIH TLV: 10 MG/M3 DUST; 9495


COPPER (SARA 313) (CERCLA)

CAS: 7440-50-8

RTECS: GL5325000

Fraction By Weight: <0.01%

OSHA PEL 0.1MG/M3 FUME/1 DUST

ACGIH TLV: 0.2 MG/M3 FUME; 9495

EPA Report Quantity: 5000 LBS

DOT Report Quantity: 5000 LBS


WATER

CAS: 7732-18-5

RTECS: ZC0110000

Fraction By Weight: 10-13%

OSHA PEL N/K

ACGIH TLV: N/K


0.02-0.04

CAS: 7440-70-2

RTECS: EV8040000

Fraction By Weight: <0.04%

OSHA PEL N/K

ACGIH TLV: N/K


INERT COMPONENTS

RTECS: 9999999ZZ

Fraction By Weight: 7-12%

OSHA PEL N/K

ACGIH TLV: N/K


ELECTRICITY PRIOR TO WORKING ON A BATTERY.

RTECS: 9999999ZZ


COMMUNICATION DEVICE IN THE WORK AREA.

RTECS: 9999999ZZ


AND FULL LENGTH FACESHIELD .

RTECS: 9999999ZZ

Hazards

LD50 LC50 Mixture:LD50 (ORAL, RAT): 214 MG/KG
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:NOTE: LEAD APPEARS ON THE NAVY LISTING
OF OCCUPATIONAL CHEMICAL REPRODUCTIVE HAZARDS. SEEK CONSULTATION
FROM APPROPRIATE HEALTH PROFESSIONALS CONCERNING LATEST HAZARD LIST
INFORMATION AND SAFE HANDLIN G AND EXPOSURE INFORMATION . ACUTE:
TISSUE DESTRUCTION ON CONTACT. MAY CAUSE 2ND AND (EFTS OF OVEREXP)
Explanation of Carcinogenicity:NOT RELEVANT.
Effects of Overexposure:HLTH HAZ: 3RD DEGREE BURNS OR BLINDNESS.
INGESTION WILL CAUSE CORROSIVE BURNS ON CONTACT. MAY BE FATAL IF
SWALLOWED. CHRONIC: INHALATION OF MISTS MAY CAUSE UPPER RESPIRATORY
IRRITATION. SIGNS AND SYMP TOMS: IRRITATION AND BURNING OF
EXPOSEDTISSUE.
Medical Cond Aggravated by Exposure:RESPIRATORY DISORDERS MAY BE
AGGRAVATED BY PROLONGED INHALATION OF MISTS.

First Aid

First Aid:SKIN/EYES: FLUSH WITH WATER FOR AT LEAST 15 MINUTES. REMOVE
CONTAMINATED CLOTHING. IF IRRITATION CONTINUES, SEEK MEDICAL
ATTENTION. INGESTION: DO NOT INDUCE VOMITING. DRINK LARGE
QUANTITIES OF MILK OR WATER. INHALATION: GIVE CPR IF BREATHING HAS
STOPPED. SEEK MEDICAL ATTENTION IMMEDIATELY.

Fire Fighting

Extinguishing Media:DRY CHEMICAL, HALON, OR CARBON DIOXIDE.
Fire Fighting Procedures:USE NIOSH APPROVED SCBA & FULL PROTECTIVE
EQUIPMENT . VENTILATE THE AREA WELL.
Unusual Fire/Explosion Hazard:HYDROGEN GAS MAY BE PRESENT. HYDROGEN GAS
AND ACID MIST IS GENERATED UPON OVERCHARGE OR IN FIRES. VENTILATE
AREA.

Accidental Release

Spill Release Procedures:STEPS TO BE TAKEN IF BATTERY IS BROKEN:
NEUTRALIZE EXPOSED BATTERY PARTS W/SODA ASH/SODIUM BICARBONATE
UNTIL FIZZING STOPS. PH SHOULD BE NEUTRAL AT 6-8. WHEN NEUTRAL,
BATTERY PARTS ARE NON-HAZARDOUS. PLACE BROKEN BATTERY IN A HEAVY
GUAGE (SUPDAT)
Neutralizing Agent:SODA ASH OR SODIUM BICARBONATE.

Handling

Handling and Storage Precautions:STORE IN A COOL, DRY AREA AWAY FROM
COMBUSTIBLES. DO NOT STORE IN SEALED, UNVENTILATED AREAS. AVOID
OVERHEATING AND OVERCHARGING.
Other Precautions:DO NOT USE ORGANIC SOLVENTS OR OTHER THAN RECOMMENDED
CHEMICAL CLEANERS ON BATTERIES.

Exposure Controls

Respiratory Protection:NIOSH APPROVED ACID MIST RESPIRATOR, IF OSHA PEL
IS EXCEEDED.
Ventilation:GEN ROOM VENT IS SUFFICIENT DURING NORM USE & HNDLG. REC 2
TO 3 ROOM AIR CHANGES PER HR TO PVNT BUILDUP OF HYDROGEN GAS.
Protective Gloves:RUBBER OR NEOPRENE GLOVES.
Eye Protection:ANSI APPROVED CHEM WORKERS GOGGS(ING 11)
Other Protective Equipment:EYE WASH FOUNTAIN & DELUGE SHOWER WHICH MEET
ANSI DESIGN CRITERIA . ACID RESISTANT APRON OR CLOTHES.
Work Hygienic Practices:DO NOT WEAR METALLIC JEWELRY WHEN WORKING
W/BATTERIES. USE NON-CONDUCTIVE TOOLS ONLY. DISCHARGE STATIC (ING
9)
Supplemental Safety and Health
SPEC GRAV: (CONTAINED IN BATTERY): 1.300+/-0.10. HAZ DECOMP PROD: CO*2
AND SULFUR OXIDES. SPILL PROC: PLASTIC BAG OR OTHER NON-METALLIC
CONTAINER. PROVIDE ADEQUATE VENT, HYDROGEN GAS MAY BE GIVEN OFF
DURING NEUTRALIZATION. WASTE DISP METH:& LOCAL C&D SALES
REPRESENTATIVE FOR MORE INFO. HAZ WASTE CODES: D002, D008.

Chemical Properties

Vapor Density:>1
Spec Gravity:SUPDAT
Appearance and Odor:COLORLESS, OILY FLUID/ACRID ODOR WHEN HOT.

Stability

Stability Indicator/Materials to Avoid:YES
STRONG ALKALINE MATERIALS, CONDUCTIVE METALS, ORGANIC SOLVENTS, SPARKS
OR OPEN FLAME.
Stability Condition to Avoid:OVERHEATING, OVERCHARGING WHICH RESULT IN
ACID MIST/HYDROGEN GENERATION.
Hazardous Decomposition Products:HYDROGEN GAS MAY BE GENERATED IN AN
OVERCHARGED CONDITION, IN FIRE/AT VERY HIGH TEMPS. IN FIRE MAY EMIT
CO, (SUPDAT)

Disposal

Waste Disposal Methods:THIS BATTERY IS RECYCLABLE, IT IS ILLEGAL TO
DISPOSE OF LEAD-ACID BATTERIES BY ANY MEANS OTHER THAN RECYCLING.
C&D PROVIDES AN ENVIRONMENTALLY RESPONSIBLE NATION WIDE LEAD ACID
BATTERY COLLECTION & RE CYCLING PROGRAM. CNTCT YOUR FED,
STATE(SUPDAT)

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.